Monitoring Systems
| HS-508 Series | Dual Trip Module |
|---|
| HS-509 Series | Single Channel Trip Module |
|---|


- Input - 0-10V DC or 4-20mA accelerometer (HS-420 Series)
- Fully configurable
- Relay inhibit
- Output - 2 trips, 4-20mA or 0-10 Volts
| HS-510 Series | Single Channel Display Trip Module |
|---|


- Input - 0-10V DC or 4-20mA accelerometer (HS-420 Series)
- Fully configurable
- Relay inhibit
- Output - 2 trips, 4-20mA, 0-10 Volts
| HS-530 Series | Single Channel Interface Module with Special Quad Output |
|---|

- Input - 100mV/g constant current accelerometers (HS-100 Series)
- Output - AC and 0-10 Volts proportional to either RMS Velocity, Envelope 'g', AC 'g' via BNC (for data collection), or AC Enveloped 'g'
- 'Sensor OK' Function
| HS-531 Series | Single Channel Interface Module with Special Quad Output |
|---|

- Input - 100mV/g constant current accelerometers (HS-100 Series)
- Output - AC and 0-10 Volts proportional to either RMS Velocity, Envelope 'g', AC 'g' via BNC (for data collection), or AC Enveloped 'g'
- 'Sensor OK' Function
- For use in the wind power application
| HS-535 Series | Single Channel Interface Module with Triple Output |
|---|


- Input - 100mV/g constant current accelerometers (HS-100 Series)
- Output - AC, 4-20 mA and 0-10 Volts proportional to either RMS Velocity, Peak 'g' or AC 'g'
- 'Sensor OK' Function
| HS-536 Series | Single Channel Interface Module with Displacement Output |
|---|


- Input - 100mV/g constant current accelerometers (HS-100 Series)
- Output - AC, 4-20 mA and 0-10 Volts proportional to either RMS Velocity and Peak to Peak Displacement
- 'Sensor OK' Function
| HS-540 Series | Voltage to Current or Current to Voltage Converter |
|---|

- Input - 0-10V DC or 4-20mA accelerometer (HS-420 Series)
- Output - 4-20mA or 0-10 Volts
| HS-550 Series | Accelerometer Power Supply and Signal Amplifier |
|---|

- Input - 100mV/g Constant Current Accelerometers (HS-100 Series)
- Output - Voltage Gain x1, x10, x100 selectable via DIL switch
- 'Sensor OK' Function
| HS-551 Series | Accelerometer Power Supply |
|---|

- Input - 100mV/g constant current accelerometers (HS-100 Series)
- Output - AC (no bias) BNC or terminals
| HS-556 Series | Single Channel 4-20mA Interface Module |
|---|

- Input - 100mV/g constant current accelerometers (HS-100 Series)
- Output - 'g' or velocity proportional to 4-20mA, AC 'g' via BNC (for data collection)
| HS-557 Series | Dual Output 4-20mA Interface Module |
|---|

- Input 1 - Dual Output Accelerometer with Temperature Sensor (HS-100T Series), 10mV/°C, PT100
- Input 2 -100mV/g constant current accelerometers (HS-100 Series)
- Output - 4-20mA proportional to temperature and velocity or 'g', AC 'g' via BNC or screw terminal (for data collector)
| HS-570 Series | Power Supply Module - Output 20 Watts |
|---|

- Powers HS-500 Series modules
- DIN rail mounted
- Input - 85 to 264 Volts AC
- Output - 24 Volts DC
- Output power - 20 watts
| HS-570 Series | Power Supply Module - Output 40 Watts |
|---|

- Powers HS-500 Series modules
- DIN rail mounted
- Input - 85 to 264 Volts AC
- Output - 24 Volts DC
- Output power - 40 watts
| HS-570 Series | Power Supply Module - Output 60 Watts |
|---|

- Powers HS-500 Series modules
- DIN rail mounted
- Input - 85 to 264 Volts AC
- Output - 24 Volts DC
- Output power - 60 watts
| HS-580 Series | Industrial Enclosure for HS-500 Modules |
|---|




- Accomodates HS-500 Series modules
- Various configurations
- Sealed to IP66
- Fan cooling
| Optional Extras | Optional Extras |
|---|
- Flashing Beacon
- Klaxton
- Custom Filters/Modules
- Wireless Retransmit